Fault Location Using the Natural Frequency of Oscillation of Current Discharge in MTdc Networks

13 Apr 2020  ·  Bhaskar Mitra, Suman Debanth, Badrul Chowdhury ·

This paper discusses a novel fault location approach using single ended measurement. The natural dissipation of the circuit parameters are considered for fault location. A relationship between the damped natural frequency of oscillation of the transmission line current and fault location is established in this paper. The hybrid dc circuit breaker (dcCB) interrupts the fault current and the line current attenuates under the absence of any driving voltage source. The line capacitance discharges into the fault at a specific frequency of oscillation and rate of attenuation. Utilizing this information, the fault location in a multi-terminal direct current (MTdc) network can be predicted. A three terminal radial model of a MTdc is used for performance evaluation of the proposed method using Power System Computer Aided Design (PSCAD)/Electromagnetic Transients including dc (EMTdc).