Combined Unbalanced Distribution System State and Line Impedance Matrix Estimation

22 Sep 2022  ·  Marta Vanin, Frederik Geth, Reinhilde D'hulst, Dirk Van Hertem ·

To address the challenges that the decarbonization of the energy sector is bringing about, advanced distribution network management and operation strategies are being developed. Many of these strategies require accurate network models to work effectively. However, distribution network data are known to contain errors, and attention has been given to techniques that allow to derive improved network information. This paper presents a novel method to derive line impedance values from smart meter measurement time series, with realistic assumptions in terms of meter accuracy, resolution and penetration. The method is based on unbalanced state estimation and is cast as a non-convex quadratically constrained optimization problem. Both line lengths and impedance matrix models can be estimated based on an exact nonlinear formulation of the steady-state three-phase network physics. The method is evaluated on the IEEE European Low Voltage feeder (906 buses) and shows promising results.

PDF Abstract

Datasets


  Add Datasets introduced or used in this paper

Results from the Paper


  Submit results from this paper to get state-of-the-art GitHub badges and help the community compare results to other papers.

Methods


No methods listed for this paper. Add relevant methods here