Optimal Dynamic Ancillary Services Provision Based on Local Power Grid Perception

31 Jan 2024  ·  Verena Häberle, Xiuqiang He, Linbin Huang, Eduardo Prieto-Araujo, Florian Dörfler ·

In this paper, we propose a systematic closed-loop approach to provide optimal dynamic ancillary services with converter-interfaced generation systems based on local power grid perception. In particular, we structurally encode dynamic ancillary services such as fast frequency and voltage regulation in the form of a parametric transfer function matrix, which includes several parameters to define a set of different feasible response behaviors, among which we aim to find the optimal one to be realized by the converter system. Our approach is based on a so-called "perceive-and-optimize" (P&O) strategy: First, we identify a grid dynamic equivalent at the interconnection terminals of the converter system. Second, we consider the closed-loop interconnection of the identified grid equivalent and the parametric transfer function matrix, which we optimize for the set of transfer function parameters, resulting in a stable and optimal closed-loop performance for ancillary services provision. In the process, we ensure that grid-code and device-level requirements are satisfied. Finally, we demonstrate the effectiveness of our approach in different numerical case studies based on a modified Kundur two-area test system.

PDF Abstract
No code implementations yet. Submit your code now

Tasks


Datasets


  Add Datasets introduced or used in this paper

Results from the Paper


  Submit results from this paper to get state-of-the-art GitHub badges and help the community compare results to other papers.

Methods


No methods listed for this paper. Add relevant methods here